6.1 Checking Three-phase Systems
58
Quick Start Manual
2.
Making 3196 settings
MEASURE
Make the following settings.
Setting Item Selections
123ch/ Wiring
3P3W3M
123ch/Clamp
1 m V/A 9661
123ch/U Range
600 V
123ch/PT Ratio
1
123ch/I Range
50 A
123ch/CT Ratio
1
UReference
400 V
Frequency
50 Hz
PLL Source
U1
U CalcType
LINE-LINE
EN50160
OFF
Select item
Select from
pull-down
menu