Error Codes
© Hirschmann Rev. I 05/22/17 190154_I.DOC
71
Error Code
Error
Cause
Elimination
EDA
Datalogger write
error
Datalogger not connected
No power supply
Wrong Dos drive status
Check CAN bus
connection
Check power supply
Connect PC terminal and
Refer to Dos drive status
list
Temporary: Press horn
quit button to work
without datalogger
EDB
Datalogger setup
error
Setup of the datalogger is
cleared (ser. crane data
file or battery buffered
RAM)
transfer data and setup
datalogger again
temporary: Press horn
quit button to work
without datalogger
EDC
Datalogger
watchdog activated
datalogger processing
time limit exceeded
Reset system
Connect PC terminal and
watch error messages
EDD
Battery empty
Battery check detected a
low voltage of the battery
change battery, after this
setup of RTC
Temporary: Press horn
quit button to work
without datalogger
EDE
Record lost
Not possible to save data
because other task saves
data at the same time
Message disappears after a
few seconds
EDF
Flash block full
Not possible to save any
more data
Message disappears after a
few seconds
EFD
LMI Watchdog
extra time
a function needs more
than 0.5 sec, e.g. Flash
PROM write
Message disappears after a
few seconds
Note:
If an error message is displayed which is not contained in above list, please contact the
competent PAT service department.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hirschmann PAT IFLEX5 and is the answer not in the manual?

Hirschmann PAT IFLEX5 Specifications

General IconGeneral
BrandHirschmann
ModelPAT IFLEX5
CategoryTouch Panel
LanguageEnglish

Related product manuals