GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 17
Calculating Current Draw and Standby Battery Installation Instructions Criteria
B200S Intelligent Sounder Base Aux Pwr
Standby: .5mA
mA
Alarm: (high vol) 35mA mA
SLC Standby .3mA mA
SLC Accessories
B200SR-LF Low Frequency Sounder Base Aux Pwr Standby: 1mA mA
Alarm: 125mA mA
B200S-LF Low Frequency Sounder Base Aux Pwr Standby .55mA mA
Alarm (high vol) 140mA mA
SLC Standby .30mA mA
B224RB Relay Base Standby/Alarm: .5mA mA mA
RTS151/151 KEY Alarm: 7.5mA
mA
RA100Z Alarm: 10mA
mA
SLC Isolator Devices
M500X (Isolator Module) (100 max.) Standby/Alarm: .45mA mA mA
B224BI Isolator Base (50 max.) Standby/Alarm: .5mA
Accessories Modules
RA-1000 Remote LCD Annunciator Standby: 20mA mA
Alarm 25mA mA
5824 Serial / Parallel Module (4 max.) Standby/Alarm: 45 mAmA mA
GFPS-6S NAC Expander (8 max.) Standby/Alarm: 10 mAmA mA
5880 LED I/O Module (8 max.) Standby: 35 mAmA
Alarm: 200 mA mA
Wireless Modules
VW-GATE Wireless Gateway Max current using external supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
A Total System Current
Auxiliary Devices
2
Refer to devices manual for current rating.
CELL-MOD. CELL-CAB-GWF Standby: 55 mA mA
Alarm: 100 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
GFPS-6/GFPS-9 Power Supply 24 VDC One input circuit: 15 mA
mA
Both input circuits: 30 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C Notification Appliances Current
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x .001): A A
F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
I Multiply lines E and H. Total alarm AH
AH
J Add lines G and I.
3
AH
Multiply by the Derating Factor x 1.25
Total ampere hours required AH
NOTES
Note 1: The Total calculation does not include the Isolator devices or accessory bases.
Note 2: If you use door holders, you do not need to calculate the door holder current for the alarm/battery standby, because the power is
removed during that time. During normal operation, the door holders draw current and must be included in the 2.5A total alarm current (1.0A
for all other conditions that can be drawn from the panel.
Note 3: Use the next size battery with capacity greater than required. ABD-RT2F draws a maximum of 500mA from Auxiliary power only
when you use the test feature. This should be considered when you determine the auxiliary power capacity but not calculated into current
requirements for day-to-day operation. The ASD-PL2FR is sold separately from the DNR. Current draw for the DNR + ASD-PL2FR is
calculated by increasing the “Number of Devices” column for each ASD-PL2FR used with a DNR.
Note 4: The DNR housing does not include a Relay circuit board. If a relay is needed, be sure to add one to the AOM-2RF & ASD-PL2FR
“Number of Devices” column for each DNR used for correct current calculations.
Note 5: The FACP supports only 5 devices w/LED’s ON. This current draw has been added to the panels alarm current.
Note 6: UL 268 7th Edition Sensitivity Level Requirements:
The models: ASD-PL3/-IV, ASD-PL3R/-IV, ASD-PTL3/-IV, detectors must be programmed with the following Sensitivity Levels to be
compliant with the UL 268 7th Edition requirements (3% is the Default).
- 1% and 1.5% for Special Applications
- 2%, 2.5% and 3% for Open Area Protection
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.3 Current Calculation Worksheet for Velociti Devices (Continued)

Table of Contents