GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 39
Mapping Overview Programming Overview
6.2 Mapping Overview
This section of the manual is an overview of mapping.
Mapping is an important concept with the control panel. In general terms, the concept of mapping is the process where you assign or link
events to outputs. Outputs activate when events occur. You do this by assigning input points to input zones, output points to output
groups and then you link or map zones and output groups.
Figure 6.1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
Figure 6.1 Mapping Overview
Options Procedures
1 - Review System Press 1 if you need to review the JumpStart
configuration.
2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason.
3 - Accept Changes
1. If you are ready to make the JumpStart
®
configuration permanent, select 3.
2. The system will ask you if the installation contains any Addressable Duct Detectors Used. If there are none,
select 2 for No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and continue with Step
3.
3. From the list that displays, select the SLC that contains the duct detectors.
4. The first photoelectric or ionization detector on the system will display. Select 1 for DUCT and 2 for Non-DUCT.
5. Press up arrow to select the next detector. Select 1 for DUCT and 2 for Non DUCT. Continue until all duct
detectors have been selected. (Note: You can move backwards through the list with down arrow).
6. When you reach the last detector on this device, press left arrow.
7. The system will ask you if there are any duct detectors used. If there are, select 1 for Yes and the message will
ask, Have All Addressable Duct Detectors Been Identified? Left arrow for “No”, Right arrow for “Yes”. If there
are no more duct detectors, continue with Step 8.
8. The system will restart with the saved JumpStart configuration.
9. After the system resets, it will use the new JumpStart configuration.
4 - Discard Changes If you want to discard the changes, and keep the configuration you had before running this JumpStart press 4.
Table 6.2 Menu Options
Input Zone Output Zone
Input
points
(SLC Devices)
Output points
(Notification Circuits)
Note 1: Due to the flexibility of the Control Panel programming, there are a number of uses
for mapping, as shown in the diagram below.
Note 2: Input Zones are mapped by Event Types to Output Groups.
Cadence patterns are assigned as part of the mapping information.
Input Points
SLC Devices
Input Zones
Cadence
Patterns
Output Groups
Output Points
Notification
and Relay
Circuit
System
Trouble
Events and
Special
System
Output Points
are assigned
to Output
Groups Only
Input Points
are assigned
to Input
Zones.
Input
points
(SLC Devices)
NOTE: Mapping cannot be programmed through annunciators and can only be programmed through HFSS Honeywell Fire
Software Suite.