GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 9
About this Manual Introduction
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the GWF-7075. Please let us know if the
manual does not meet your needs in any way. We value your feedback!
1.2.1 Terms Used in this Manual
The following terminology is used with the GWF-7075 system. For additional information on the compatible devices, refer to the Com-
patibility Addendum to Gamewell-FCI Manuals, P/N:9000-0427-L8.
1.3 Compatible Products
The chart below lists the products available from Gamewell-FCI for use with the GWF-7075.
Term Description
SLC Signaling Line Circuit
Module The term module is used for all hardware devices except for SLC addressable devices and notification
appliances. This includes the GWF-7075 panel itself.
Input Point An addressable sensing device, such as a smoke or heat detector or a contact monitor device.
Input Zone A protected area made up of input points.
Output Point
(or Output Circuit)
A notification point or circuit for notification appliances. Relay circuits and auxiliary power circuits are
also considered output points.
Group (or “Output Group”) A group of output points. Operating characteristics are common to all output points in the group.
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones
and special system events. See Appendix Appendix B:, “Cadence Patterns” for additional information.
Mapping Mapping is the process of specifying which outputs are activated when certain events occur in the
system. Section 6.2 explains mapping in detail.
SWIFT Smart Wireless Integrated Fire Technology
Table 1.2 Manual Terminology
NOTE: For additional information on compatible devices, refer to the Compatibility Addendum to Gamewell-FCI Manuals,
P/N: 9000-0427-L8.
Type of Device Model Description
Velociti mode
Addressable SLC
Devices
For a list of compatible devices, refer to Section 5.1 and the Compatibility Addendum of Gamewell-FCI Manuals,
P/N:9000-0427-L8.
SWIFT Wireless
SLC Devices
See Section 5.2 for a list of compatible devices
Other Modules 5824 Serial/Parallel Printer
Interface Module
Allows a printer to be attached for the on-site event logging. Maximum of four 5824s
per control panel.
GFPS-6S NAC Expander Provides 4 additional Notification Appliance Circuits/Auxiliary power. (Up to 8 per
GWF-7075 system.)
RA-1000 and RA-1000R LCD
Annunciator
4 x 20 Remote LCD annunciator can be used in any combination, up to a total of 8
devices on one panel.
5860TG and 5860TR Trim Ring Trim ring kits for surface mounting the RA-1000 annunciator. 5860TG is gray; 5860TR
is red.
5880 LED Driver Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition
the 5880 has eight generic switch input points.
Wireless VW-GATE Velociti Wireless SWIFT Gateway
VW-DIS-D SWIFT Wireless Display Driver
WSD-P Velociti Wireless Photoelectric Smoke Detector requires 1 B210W base
WSD-ACCLIMATE Velociti Wireless Multi criteria Sensor Intelligent SWIFT Acclimate detector
WTD-RH Velociti Wireless Thermal Detector Rate-of-Rise, 135° Requires one B210W base
WTD-H Velociti Wireless Thermal Detector, 135° fixed. Requires one B210W base for
installation
WAM-MM Wireless Monitor module
B210W Wireless 6” (15.23cm) flanged Base
Miscellaneous HFSS Honeywell Fire Software
Suite
For communication and panel programming with a Windows-based computer. Enables
remote viewing of detector status and event history.
7860 Telephone Cord RJ31X cord for connecting phone line to the GWF-7075
7628 UL Listed End-of-line resistor.
DF-50 Dead Front insert.
CELL-MOD Cellular board with Plastic Enclosure
CELL-CAB-GWF Cellular board with Metal Enclosure
MRD-1 Manual Releasing Disconnect Assembly Instructions (P/N:LS10231-000GE-E)
Table 1.3 GWF-7075 Compatible Products