System Options Programming
7.3.3 Point Programming for 5880 Modules
To program for a 5880 Module points, follow these steps:
1. Enter the Installer Code.
2. Select 7 for the Program Menu.
3. Press 4 to enter the Point Menu.
4. Press the <Up> or <Down> arrows to select the desired module. Refer to Section 6.5 for available choices. Press <Enter>.
5. Enter the Point Number, then press <Enter>.
6. Press the <Up> or <Down> arrows to select the type (Notification or unused). Press <Enter>.
7. Press the <Up> or <Down> arrows to select the desired Group, then press <Enter>.
8. Edit Module Name. See Section 7.2.1. Or, press the <Right> arrow to bypass the Module Name edit.
9. Repeat Steps 1 through 8 for all points.
Figure 7.6 Programming Points Screen for 5880 Modules
7.4 System Options
This section of the manual explains how to customize software options that affect the general operation of the system.This includes such
options as follows:
Refer to each individual subsection for complete instructions.
7.4.1 Communication Options - Auto Test Time
To access the Auto Test Time screen:
1. Enter the Installer Code.
2. Select 7 for the Program Menu.
3. Select 5 for the System Options.
4. From the next menu, select 1 for Communication Options.
5. Select 1 for the Auto Test Time.
6. Enter the hour you want the control panel to send an Automatic Test Report (or press the <Up> or <Down> arrows), then press
<Enter>.
7. Enter the minutes (or press the <Up> or <Down> arrow keys), then press <Enter>.
8. To select AM or PM, press the <Up> or <Down> arrow keys, then press <Enter>.
9. To select the Report Time Interval, press the <Up> or <Down> arrow keys, then press <Enter>.
10. Time Interval selections are 24hr, 12hr, 6hr and 4 hr.
NOTE: AM and PM are only available if the panel “Clock Options” are set for AMPM mode. Otherwise, the clock is set in military time and
you cannot select AMPM.
7.4.2 Phone Lines
To access the Phone Lines screen:
1. Enter the Installer Code.
2. Select 7 for the Program Menu.
3. From the Program Menu, select 5 for the System Options.
4. Select 1 for Communication Options.
5. Select 2 for the Phone Lines Menu.
6. To select the Phone Line you want to edit (1 or 2), press the <Up> or <Down> arrows, then press <Enter>.
Figure 7.7 Phone Lines Editing Screen
.
M01 POO1 NOTIF
G01
MODULE_1 CKT_1
<Enter Pt or <=Exit>
Select a name for the Point.
Select circuit to program.
Select NOTIF or UNUSED.
Select an output group for
this Notification Point.
• Communication Options • Daytime /Nighttime Sensitivity • Holiday Schedule • Telephone and Reporting Account
Line: 1 N
P: Rings:06
D:TT Options:U N Y N
<Dialing Prefix>
Use this field to enter a Dialing
Prefix. You can enter up to 9
characters to allow for PBX
dial-out codes, a pause etc.
Type of Dial Options:
-Touch Tone
-Pulse
-Both
Options:
-U = U.S.
-E = European
-U.S. Format = 60/40 msec Make/break
-European Format = 66/34 msec make/break
Monitor Line Y/N
Dial Tone Detection Disabled Y/N
Phone Line Unused Y/N
Use this field to identify the number of
rings before a panel acknowledges the
call from the computer.
Answering Machine Bypass Y/N
Phone Line to edit
(selected in previous screen
To enable, enter Y.
To disable, enter N.
(Except as noted).