54 GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Programming Point
7.3.2 Point Programming for an Internal or an External Power Module
To program for an internal or external Power Module Points, follow these steps:
1. Enter the Installer Code.
2. Select 7 for the Program Menu.
3. Press 4 to enter the Point Menu.
4. Press the <Up> or <Down> arrows to select the desired module. Press <Enter>. Refer to Section 6.5 for available choices.
5. <Enter> the number of the circuit or point you want to edit. Refer to Table 7.5 for available selections. Press <Enter>.
6. To select the type, press the <Up> or <Down> arrows, then press <Enter>.
7. To select the function, press the <Up> or <Down> arrows, then press <Enter>.
8. To select the group, press the <Up> or <Down> arrows, then press <Enter>.
9. Edit point name. Press the <Right> arrow to bypass the Point Name Edit. See Section 7.3.
10. Repeat Steps 1 through 10 for all circuits.
Choices Type Selections
Function Selections
for each Type
Comments
Enter Point or Circuit
Select Type UNUSED
NOTIF OUT
CTRL CKT
AUX PWR CONSTANT Constant auxiliary power.
RESETTABLE Resettable auxiliary power.
DOOR Door holder auxiliary power.
AUX SYNC Sounder Sync auxiliary power for System Sensor
B SWITCH* MAN PULL Refer to comments column of
Table 7.4 for description of these options
Latch or Non-latching feature only appears for
waterflow, supervisory, tamper, zone aux1,
zone aux2, system aux1, and system aux2
WATERFLOW
SUPERVSY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
STATUS POINT Non-latching - Used to activate an ancillary
Output Group that does not active alarm, sound
PZT, display status or report events. Reset has
no affect on this point
A SWITCH* Same as B SWITCH
Select Type B DETECTOR* 2-WIRE SMOKE Used for Class B, 2-wire detectors.
4-WIRE SMOKE Used for Class B, 4-wire detectors.
CO 4-WIRE DET Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET Latching or Non-latching used for Class B, 4-wire CO
Supervisory detectors
A DETECTOR* 2-WIRE SMOKE Used for Class A, 2-wire detectors.
4-WIRE SMOKE Used for Class A, 4-wire detectors.
CO 4-WIRE DET Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET Latching or Non-latching used for Class A, 4-wire CO
Supervisory detectors
Select Group Group or Zone selection will appear depending on the type
selected
Edit Name Edit name. See Section 7.3.2
*Only applicable on
Table 7.5 Menu choices for Internal/External Power Modules