48 GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Section 7: Programming
To manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All
options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
7.1 UL 864 Programming Requirements
7.2 Modules
This section lists the options available under the Module Option in the Program Menu. The types of modules available for the control
panel are as follows:
7.2.1 Edit Modules
If you select Edit Modules, you can edit the module name and class of wiring (Class A or Class B) features. To edit an existing module,
follow these steps:
1. Enter the Installer Code.
2. Select 7 for Program Menu.
3. Press 1 to enter Module menu.
4. Press 1 to edit a module.
5. Use the <Up> or <Down> arrows to select the module you want to edit.
7.2.2 Editing Module ID
1. Press the <Up> or <Down> arrows key to modify the Module ID.
NOTE: You cannot edit the Module ID on Internal devices.
7.2.3 Naming Modules
You can assign an English name to a hardware module to make it easier to recognize on a display.
1. To edit a Module Name, press the <Up> or <Down> arrows to select each character for the module’s name (or press the <Right>
arrow to bypass the name edit). Press the <Right> arrow to move the cursor to the next character.
NOTE: To edit names, refer Appendix Appendix A:.
Figure 7.1 Edit Module Name Programming Screen Example
IMPORTANT!
Before you complete any customized programming, you must first run JumpStart
®
Auto-programming. After JumpStart is run, thor-
oughly test the system. The reason you test the system after JumpStart Auto-programming is to activate JumpStart Auto-programming
to automatically program the system, searching for and configuring all SLC and SBUS devices it finds. JumpStart allows you to con-
firm the integrity of the installation prior to performing any custom programming. After you determine the hardware is properly
installed, you can perform custom programming.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES: This product
incorporates field programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Programming Option Menu Item
Permitted in UL
864 (Y/N)
Possible Settings Settings Permitted in UL 864
Time Options Auto-Resound Yes 4 or 24 hrs 4 hours if using SWIFT devices
Time Options Low AC Report Delay Yes 0–30 hours 1–3
D i s p l a y O l d e s t E v e n t Y ( E n a bled) Yes Yes & No Yes
N (Disabled) No Yes & No No
Alarm Verification Alarm Verification Yes 60-250 (confirmation period) 60
Table 7.1 Programming Criteria
• RA-1000 LCD Annunciator • 5824 Serial/Parallel input/output • 5880 LED Input/Output module • GFPS-6S NAC Expander