GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 47
Programming Menu Quick Reference Programming Overview
System
Options
Communication
Options
Phone Lines For each phone line (1 & 2) select:
Dialing Prefix Up to 9 digits *none
# of Answer Rings Range: 00-15 *06
Select Dialing Option
TT *TT
TT/PL
PULSE
Rotary Pulse Format
U = 60/40 *U
E = 66/34
Dial Tone Disabled Y or N *N
Monitor Line Y or N *N
Answering Machine Bypass Y or N *N
Phone Line Unused Y or N *N
Edit Ethernet IP Address
Section , “Edit
Ethernet”
Subn MaskSubNet
Default Gateway
DHCP Enable
AlarmNet
Timers
Ethernet Supervise
75 sec,90 Sec,3 min,None
5 min,1 hr, 24 hrs,30 days,
*5 Minutes
Section ,
“AlarmNet
Timers”
Cellular Supervise 24Hrs, 30 days, none *24 Hours
Old Alarm Time
10 min,15 min,30 min.,
1 hr,2 hrs,4 hrs,8 hrs,
12 hrs, 24hrs, none
*30 Minutes
System
Options
con’t
Communication
Options
Phone Line
Gains
Dialing
High
*High
Section ,
“Phone Line
Gains”
Low
Normal
Reporting
Low
*LowNormal
High
Time Options
Water Flow
Delay
0 - 90 Seconds *1 sec
Water Flow delay is the
number of seconds before
a water flow alarm is
generated.
Section , “Water Flow Delay”
Alarm Verify 60 to 250 seconds *60 sec Section , “Alarm Verify”
Low AC Report
Time
0 - 30 hours *3 hrs Section , “AC Report Delay”
AC Freq:
50 Hz
*60Hz Section , “AC Line Frequency”60 Hz
Internal
Clock Display
Format
AM/PM
*AM/PM
System Clock Format (AM/PM or
military). Section , “Clock Display
Format (AM/PM or Military)”
MIL
Auto-resound
4 hours
*24 hours
Section , “Auto-Resound (4 or 24
hours)”
24 hours
Miscellaneous
Options
SYNC Strobes
when Silenced
Y
*N
Section , “Strobes Active when
Silenced”
N
Auto Display
Events
Y
*N Section , “Auto Display Events”
N
Daylight Saving
Options
Auto Daylight
Saving Time
Y
*Y
Section , “Automatic Daylight Saving
Adjustment”
N
DST Start
Select week: 1st, 2nd, 3rd, 4th or Last Select month
Section , “Daylight Saving Time Start
and End”
DST End
Edit Banner
Refer to
Appendix B
Section 7.6.7
SLC Family Velociti Section 7.6.8
Jump
Start
AutoPrg
Y (Yes)
N (No)
Section 7.7
Restore
Defaults
Y (Yes)
N (No)
See Section 7.8
*Default NOTES
Note 1: Available on Internal SLC.
Note 2: Available with SLC Family as Velociti
Note 3: Requires wireless Gateway.
Note 4: AUX SYNC setting is only applicable for the B200S Sounder Base.
Menu Options/Defaults Comments
Table 6.5 Programming Menu Options (Continued)