Section 1: Introduction
The Gamewell-FCI
®
, GWF-7075 is an Addressable Control/Communicator, Fire Alarm Control Panel (FACP) that complies with the
UL Standard 864. The GWF-7075 consists of two models.
• GWF-7075 (red) cabinet
• GWF-7075B (black) cabinet
*All references to GWF-7075 within this manual are applicable to the GWF-7075B.
1.1 Overview of Basic System
1.1.1 Hardware Features
The GWF-7075 panel includes the following hardware features.
• One signaling line circuit (SLC) that supports Velociti mode devices.
• The control panel’s SLC supports 75 Velociti detectors and 75 Velociti modules.
• The GWF-7075 is capable of outputting 2.5A of output power during alarm activation through two sets of terminals used for
notification appliance circuits or auxiliary application.
Each circuit is Class A power-limited per UL Standard 864 and can source up to 2.5A during alarm activation. The constant
auxiliary power load must not exceed 1A for normal standby.
• Built-in dual phone line, digital alarm communicator/transmitter (DACT), IP or optional cellular technologies.
• Reports events to central station by point or by zone.
• UL Listed for pre-action and deluge releasing systems.
• Two general purpose Form C programmable relays.
• One Form C Trouble Relay.
• Basic system operation can be performed from the on-board, or any remote annunciator.
• Up to 20 user profiles can be programmed, each having custom access code, and main menu items.
• Can be used with any combination of up to 8 Model RA-1000 Remote LCD Annunciators (sold separately).
• Can be used with Model 5880 for a total of eight devices on one control panel. See Section 4.7 and Figure 4.20 for additional
information on these models.
• 125 software zones, 125 output groups.
• Add four Notification/Auxiliary power circuits with each GFPS-6S NAC Expander. See note below.
1.1.2 Features
• Advanced smoke detector features:
– Automatic drift compensation
– Maintenance alert region
– Point status meets calibrated smoke test requirements for NFPA 72
•“JumpStart
®
” feature for easy programming
• Non-volatile event history stores 1000 events
• A choice of output patterns available for notification outputs, including Temp 4 along with ANSI 3.41 temporal signal
• Built-in synchronization appliance support for AMSECO, Gentex
®
, Wheelock
®
, or System Sensor
®
1.1.3 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
NOTE: Output Power:
In the Alarm Condition, the total output power for both circuits must not exceed 2.5A.
For all other activation conditions (for example, Supervisory, Trouble etc.), the total output power for both circuits must not
exceed 1.0A.
NOTE: The system can support a maximum of eight intelligent power modules, model GFPS-6S.
Model/Module Description Local Releasing
Remote
Station
Auxiliary
Central
Station
Emergency
Signaling
GWF-7075RB Main board YYYYYY
GFPS-6S NAC expander O Y O O O O
5220 Direct connect module NNNYNO
GWF-7075CAB /
GWF-7075CABB
Enclosure YYYYYY
Cell-Mod, Cell-CAB-GWFCellular transmitterOOOOOO
Note: Y = YES, N = NO, O = OPTIONAL
Table 1.1 NFPA Requirements for GWF-7075