GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 67
Operation Mode Behavior Conditions System Operation
Alarm
A smoke detector goes into
alarm or a pull station is
activated.
CO detector
goes into
alarm.
If more than 3
categories are
active at a
single time
screen will
display as shown.
The communicator seizes control of the phone
line and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices attached
to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this one.
Press the down arrow to view the alarm. A
screen similar to this one displays.
Press SILENCE and enter an access code (or
activate the key) to silence the annunciator (and
any notification devices attached to the system).
When the alarm condition clears, press RESET
and enter a code (or activate the key) to restore
the panel to normal.
Supervisory
The system detects a
supervisory condition.
The communicator seizes control of the phone
line and calls the central station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second on,
one second off.
SUPERVISORY LED flashes.
The LCD displays a screen similar to this one.
Press down arrow to view the supervisory
condition. A screen similar to this one displays.
Press SILENCE and enter an access code (or
activate the key) to silence the annunciator.
Once the supervisory condition has been
corrected, the system will restore itself
automatically.
Supervisory
The system detects a
supervisory condition with a CO
detector
Operation
Mode
Operation Mode
Condition
System Behavior
Operation Mode Troubleshooting
Options
Table 8.4 : Operation Mode Behavior (Continued)