EasyManua.ls Logo

Honeywell Gamewell-FCI GWF-7075 - Page 75

Honeywell Gamewell-FCI GWF-7075
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 75
Receivers Compatible with the Control Panel Reporting
Water flow switch trouble Restore SJ Zone # SJNN000ZZZ 3 373 00 Zone #
Zone-based AUX1 switch alarm UA Zone # +
1000
UANN001ZZZ 1 140 01 Zone #
Zone-based AUX1 switch alarm re-
store
UH Zone # +
1000
UHNN001ZZZ 3 140 01 Zone #
Zone-based AUX1 switch trouble UT Zone # +
1000
UTNN001ZZZ 1 373 01 Zone #
Zone-based AUX1 switch trouble
restore
UJ Zone # +
1000
UJNN001ZZZ 3 373 01 Zone #
Zone-based AUX2 switch alarm UA Zone # +
2000
UANN002ZZZ 1 140 02 Zone #
Zone-based AUX2 switch alarm
restore
UH Zone # +
2000
UHNN002ZZZ 3 140 02 Zone #
Zone-based AUX2 switch trouble UT Zone # +
2000
UTNN002ZZZ 1 373 02 Zone #
Zone-based AUX2 switch trouble
restore
UJ Zone # +
2000
UJNN002ZZZ 3 373 02 Zone #
Point Events: For Velociti devices, sensors 1–99 are reported as Points 1–99, modules 1–99 are reported as Points 201–299.
An unexpected SLC device has been
detected
pi Exp. ID XE Point # XENNXXPPPP 1 380 Exp. ID Point #
An unexpected SLC device has been
removed
pi Exp. ID XI Point # XINNXXPPPP 3 380 Exp. ID Point #
Auxiliary power disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Auxiliary power enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Auxiliary power Trouble pi Exp. ID FT Point # FTNNXXPPPP 1 320 Exp. ID Point #
Auxiliary power trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 320 Exp. ID Point #
Background Music Switch is Trouble pi Exp. ID UT Point # UTNNXXPPPP 1 379 Exp. ID Point #
Background Music Switch is Trouble
Restored
pi Exp. ID UJ Point # UJNNXXPPPP 3 379 Exp. ID Point #
Background Music Switch is
Disabled
pi Exp. ID UB Point # UBNNXXPPPP 1 580 Exp. ID Point #
Background Music Switch is
Enabled
pi Exp. ID UU Point # UUNNXXPPPP 3 580 Exp. ID Point #
CO Detector Trouble pi Exp. ID GT Point # GTNNXXPPPP 1 373 Exp. ID Point #
CO Detector Trouble Restore pi Exp. ID GJ Point # GJNNXXPPPP 3 373 Exp. ID Point #
CO Detector Disabled pi Exp. ID GB Point # GBNNXXPPPP 1 571 Exp. ID Point #
CO Detector Enabled pi Exp. ID GU Point # GUNNXXPPPP 3 571 Exp. ID Point #
Detector Alarm pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Detector Alarm restore pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Detector Disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Detector Enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Detector Trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Detector Trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Detector CO Alarm pi Exp. ID GA Point # GANNXXPPPP 1 162 Exp. ID Point #
Detector CO Alarm Restore pi Exp. ID GH Point # GHNNXXPPPP 3 162 Exp. ID Point #
Detector CO Supervisory Alarm pi Exp. ID GS Point # GSNNXXPPPP 1 200 Exp. ID Point #
Detector CO Supervisory Alarm
Restore
pi Exp. ID GR Point # GRNNXXPPPP 3 200 Exp. ID Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module ID
# (If Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 9.2 : Reporting Formats Table (Continued)

Table of Contents