EasyManuals Logo

Honeywell HCE 80 User Manual

Honeywell HCE 80
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Installation and configuration
7
Antenna connection
Cable length Max. 30 m
Cable cross-section
JE-LiYCY 2x2x0.5 mm²;
JE-Y(St)Y 2x2x0.8 mm;
2x0.5 mm²
Stripping length 5.5 mm
Terminal range of
the connectors
0.07–1.54 mm²
Heating/cooling, boiler feedback
Cable length Max. 100 m
Cable cross-section
JE-LiYCY 2x2x0.5 mm²;
JE-Y(St)Y 2x2x0.8 mm;
2x0.5 mm²
Stripping length 5.5 mm
Terminal range of
the connectors
0.07–1.54 mm²
Tab. 2: Permissible cable types and lengths
6.2.2. Connecting power cable
DANGER
Danger to life through electric
shock!
Contacts that are open are live.
Ensure that the cable is deenergized.
Select a suitable cable in accordance with Table 2 for the
power supply.
Strip the connections 7 mm (see fold-out page, Fig. 7).
Connect the cable to the connector in
accordance with the graphics (see
fold-out page, Fig. 4 (12)).
Plug the connector into Socket 12
(see the fold-out page, Fig. 4).
L
Secure the cable with the cable clamp.
Installation Disassembling
6.2.3. Connecting the thermal actuators
WARNING
Damage to the underfloor heating
controller!
Take the technical data into account
at thermal actuators: Total of 3 A
maximum current, 250 mA continu-
ous current per zone.
Each zone can control up to 3 actuators. 3 actuators can be
connected directly for zone 1, 2 for zone 2 and 1 each for
zones 3 through 5. One connection for the expansion mod-
ule is available for each of the zones 6 through 8.
If more than 11 thermal actuators are to be connected to the
underfloor heating controller, the cables of the actuator must
be wired in a distribution box.
Lay the actuator cables to the distribution box.
Connect the actuator wires.
Break out the openings for
the cables on the housing
using a diagonal cutter.
Strip the connections 5.5 mm (see
fold-out page, Fig. 6).
Insert the connecting cables of the
actuators into the cable openings of
the connectors.
Close the terminators.
Plug the connectors into the sockets of the corresponding
zones (see the fold-out page, Fig. 4 (Z1 -Z8)).
Clamp the cables into the stress relief clamp.
Secure the cable with the cable clamp.
Installation Disassembling
6.3. Boiler feedback
6.3.1. Connecting the boiler feedback via
an analog output (only HCE 80/
HCC 80) to external controllers
The analog output voltage changes depending on the valve
position.
Strip the connections 5.5 mm (see fold-out page, Fig. 5).
Connect the boiler feedback
in accordance with the fol-
lowing graphics (see the
fold-out page, Fig. 4 (9)).
TW
H/C
B+
Boiler feedback is possible with the controllers MCR 200,
MCR 40, ZG 252 N, Panther and Smile.
Connect the controller inputs in accordance with the en-
closed instructions (earth input to Terminal 6, temperature
input to Terminal 5 of the underfloor heating controller).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HCE 80 and is the answer not in the manual?

Honeywell HCE 80 Specifications

General IconGeneral
BrandHoneywell
ModelHCE 80
CategoryController
LanguageEnglish

Related product manuals