- 14 -
4) Connection of Digital outputs
Fig. 2.7.4 Digital outputs Connection
DO1
DO2
DO3
DO4
DO5
DO9
DO10
DO11
DO12
DO_COM1
DO6
2
DO_COM2
3
DO7
4
DO8
5
6
7
8
9
10
11
12
13
14
1
1
2
3
5
4
6
7
8
9
11
10
12
13
14
+
DC 24V
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
L
oa
d
-
+-
+-
+-
+-
+-
+
-
+-
+-
+-
+-
+-
CAUTION
Open-collector output of IPC5000 is designed for 30VDC and less than 100mA. When
using a relay as a load, use a relay for 24VDC. 24 volt power supply needs supplied by
user. Supply should have a minimum current rating of 1.5A.