- 48 - 
3.9 Compensation set screen 
This screen comes from Fig 3.8.1 
 
 
 
 
 
 
 
 
 
 
 
   Fig. 3.9.1 Compensate set screen 
 
(1) ITEM Number Display: displays up to 10 
(2) CP set (Correction Point):  
z  Enters Correction Point input value at the specified item position. Typing in the input value 
with the keypad on the left and pressing ‘ENT’ key changes and saves the value. ‘ESC’ key 
cancels the process. Enter value in Engineering units. Also, input value can be moved with 
the direction keys of the keypad on the right. 
      Range = -5.0% to 105.5% of PV input range 
 Default = 0 
(3) BIAS (Enter value in Engineering units) 
z  Enters BIAS input standby status at the specified item position.   
z  Range  
LIN Bias = -99.9 to +99.9   
          Default = Refer to Table 3.6.1 
APPRX = -5.0% to 105.0% of input range 
          Default = Refer to Table 3.6.1 
 
        Table 3.6.1 Defaults of compensation 
LIN. APPRX 
No 
CP set  BIAS  CP set  BIAS 
1  105% of Input range  0.0  -5% of Input range  -5% of Input range 
2~10  105% of Input range  0.0  105% of Input range  105% of Input range 
2003.01.23 
COMPENSATE 
EXIT 
12 H 59 M 
ESC
―
0 1
2 3
4 5
6 7
8 9
.
ENT
No. BIAS  DISPL