- 22 -
Continued
Instrument input range
Input type
Input
range
code
ºC ºF
Measurement accuracy:
± 0.1% of span typical(± 1 digit for display)
K1 -200.0~200.0 -328.0~392.0 +/-0.1%FS Below 0ºC : +/-0.2%FS
K2 0.0 ~ 1200.0 32.0~2192.0 +/-0.1%FS
K3 0.0~800.0 32.0~1472.0 +/-0.1%FS
K4 0.0~400.0 32.0~752.0 +/-0.1%FS
K(CA)
K5 0.0~1316.0 32.0~2400.0 +/-0.1%FS
J(IC) J 0.0~800.0 32.0~1472.0 +/-0.1%FS
R R 0.0~1600.0 32.0~2912.0 +/-0.1%FS
S S 0.0~1600.0 32.0~2912.0 +/-0.1%FS
B B 0.0~1800.0 32.0~3272.0 +/-0.1%FS
+/-4.0%FS at 0 to 260ºC
+/-0.15%FS at 260 to 800ºC
E(CRC) E 0.0~800.0 32.0~1472.0 +/-0.1%FS
T(CC) T -200.0~300.0 -328~572.0 +/-0.1%FS +/-0.3%FS at –200 to -45ºC
N N 0.0~1300.0 32~2372 +/-0.1%FS
W1 W1 0.0~1200.0 32~2192 +/-0.1%FS
W2 W2 0.0~2300.0 32~4172 +/-0.1%FS
Thermo
couple
C C 0.0~2300.0 32~4172 +/-0.1%FS
* FS : Full Scale