- 57 -
(4) ALARM ACTION : Selects alarm condition.
z RUN : Alarm output enabled at ‘RUN’ mode.
z ALL : Alarm output enabled at all time.
(5) ALARM Assign to : Selects channel for operation. It is available for IPC5000D.
(6) ALM ASSIGN : Registers the set alarm event to actual digital output number.
z If the value is zero, the mode event is not assigned to a digital output. So To cancel the
assigning, set the value to zero.
z Digital output number assigned by REGISTRATION number is same with Mode Event.
Refer to Table 3.11.2
(7) Data set part related to INNER alarm type.
(7-1) Event type number set
z Sets event type number for OFF/ON operation of digital output. Event type number
can be set by Keypad directly or Up and Down arrow button.
z Whenever Up and Down arrow button is pushed, (7-2) of figure 3.12.1 displays
operation description of the event type. So event type for operation can be selected.
z Refer to Table 3.12.1 for Description by Event type number.
(7-2) Event type number description
z Explains the operation of selected event type number.
z Refer to Table 3.12.1 for more detail.
(7-3) Operation Point or Max value
z The operation poiont for OFF/ON is changed according to event type number.
z Refer to Table 3.12.1 and 2 for more detail.
(7-4) Differential or Min value
z The operation poiont for OFF/ON is changed according to event type number.
z Refer to Table 3.12.1 and 2 for more detail.
(7-5) Delay time
z Sets delay time for OFF/ON.
z Set range : 1 ~ 99 seconds