20 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Programming Basic Program
The Modify Point and Delete Point screens let you edit or delete points for a detector, a monitor or
control module, or NAC. To select a point, follow these steps:
The next four sections describe how to program the points selected.
Modify an Addressable Detector Point
This section contains a sample detector programming screen, detector default selection, and
instructions for modifying a detector point. Autoprogram default values for a detector are shown:
To select Do the following Refer to
an addressable
detector
Press
Type the SLC number (1 or 2) and
detector (D) and address (001-159)
Press
“Modify an Addressable Detector
Point” on page 20.
an addressable monitor
module
Press
Type the SLC number (1 or 2) and module
(M) and address (001-159)
Press
“Modify an Addressable Monitor
Module Point” on page 22.
an addressable control
module
Press
Type the SLC number (1 or 2) and module
(M) and address (001-159)
Press
“Modify an Addressable Control
Module Point” on page 23.
a NAC Press
Type the NAC address (01-04)
Press
“Modify NAC Points” on page 24.
Table 2.2 Detector Program Values
Field Description Set as Follows
Type Code Detector function
specification -
SMOKE(PHOTO) in example.
Press the
NEXT or PREVIOUS Selection keys to scroll through valid detector
Type Code selections. See F.4.2 on page 112 for lists and descriptions.
Custom
Label
20 character custom label. Change by placing the cursor into the first space of the field using the arrow
keys, then typing the descriptor. DETECTOR ADDR 1D101 is the
autoprogram default custom label for the detector at address 101 on SLC 1.
12 spaces for extended custom label
PROGRM SMOKE(PHOTO) DETECTOR ADDR 1D101
03 __ __ __ __A8P8AV 1D101
Blinking Type Code selection
CBE list
(five zones)
D (detector)
SLC address (001-159)
20-character user-editable custom label (in
this example, autoprogramming has used
the first 19 and left a space at the end.)
SLC Loop number
Alarm sensitivity level
Pre-alarm sensitivity level
Cooperative multi-detector
mode indicator
Alarm verification setting