Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
5
Refer to the local or national regulations relative to the installation at the site. For Europe see EN60079-
29-2, EN60079-14, EN45544-4 and EN61241-14.
This equipment is designed and constructed as to prevent ignition sources arising, even in the event
of frequent disturbances or equipment operating faults.
The sensor head must be fitted with the supplied weather protection and mounted so that the sinter is
pointing downward to provide ingress protection IPX6.
The weather protection is a potential electrostatic charging hazard. The manufacturer’s instructions
should be observed.
The transmitter has a potential electrostatic charging hazard. To minimize the risk of electrostatic
discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges, e.g. ensure
that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary
The purchaser should make the manufacturer aware of any External effects or Aggressive substances
that the equipment may be exposed to.
The equipment including the flameproof joints is not intended to be repaired.
When choosing cable and cable gland or conductors in conduit, user should take into account
temperature range. Note that it should be greater than at least 90 °C.
Note: The control card must have a suitably rated fuse.

Other manuals for Honeywell Sensepoint XCD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Sensepoint XCD and is the answer not in the manual?

Honeywell Sensepoint XCD Specifications

General IconGeneral
TypeFixed Gas Detector
Ingress ProtectionIP66/67
DisplayLCD
Output4-20 mA, Relay
CertificationATEX, IECEx
Sensor TypeElectrochemical, Infrared
Humidity0 to 99% RH (non-condensing)
MaterialStainless Steel
Detection PrincipleDepends on Sensor Type
Power Supply24 VDC nominal (17-32 VDC)