Page 6 ST 800 SmartLine Pressure Transmitters User’s Manual Revision 10
2.2.3 Safety Integrity Level (SIL)
The ST800 is intended to achieve sufficient integrity against systematic errors by the manufacturer’s
design. A Safety Instrumented Function (SIF) designed with this product must not be used at a SIL
level higher than the statement, without “prior use” justification by the end user or diverse technology
redundancy in the design. Refer to the ST 800 & ST 700 Safety Manual, 34-ST-25-37, for additional
information.
2.2.4 Plugged Impulse Line detection (PILD)
STA, STD, STG, and STF800 models are offered with a PILD option which provide indication of a
plugged impulse line or process connection. When used in conjunction with a basic or advanced
display, a non-critical diagnostic indication appears on the integral display. For units without an
integral display, an indication can be seen via the host or hand held device when HART Protocol is
utilized.
This diagnostic detects clogged or plugged impulse lines. Plugged impulse line detection (PILD) is
based on statistical models which continuously compare baseline, or normal, operating noise patterns
to check for statistically significant changes when one or both (DP) impulse lines become clogged.
See Section 5.6 for details on PILD Option licensing.

Table of Contents

Other manuals for Honeywell ST 800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ST 800 and is the answer not in the manual?

Honeywell ST 800 Specifications

General IconGeneral
BrandHoneywell
ModelST 800
CategoryTransmitter
LanguageEnglish

Related product manuals