Page 30 ST 800 SmartLine Pressure Transmitters User’s Manual Revision 10
Table 10 – Diagnostics Menu
All Diagnostics menu items are Read Only.
<Return> Return to the Level 1 menu
FAULT: There is a problem with the
Meterbody
FAULT: There is a problem with the
Electronics Module (HART, DE, or FF)
FAULT: There is a problem with the
interface between the Meterbody and
the Electronics Module.
Shows the number of Non-Critical
Diagnostics that are currently active
Normal indicates that the Loop Output
reflects the current value of the PV.
FIXED OUTPUT indicates that the Loop
Output of the transmitter is manually set
a fixed value, probably due to a DAC
Trim or Loop Test operation that is
currently in progress.
EXCESSIVE: Input applied exceeds
5% of expected value (as defined by
LRV).
EXCESSIVE: Input applied exceeds
5% of expected value (as defined by
URV).
LOW: Supply voltage is below the low
specification limit
HIGH: Supply voltage is above the
high specification limit.
OVERLOAD: Input pressure is greater
than 200% URL (DP) or 150% URL
(GP, AP)
OVERTEMP: Meterbody temperature
is greater than 125C
OVERTEMP: Electronics temperature
is greater than 85C
SUSPECT: The interface between the
Meterbody and the Electronics Module
is experiencing intermittent
communication failures.
The transmitter has not been calibrated
by the factory.
The DAC has not been compensated
for temperature effects. This is a factory
operation.