Revision 10 ST 800 SmartLine Pressure Transmitters User’s Manual Page 31
It is applicable for DP Transmitter only.
OK: Blockage is not detected
BLOCKED: Blockage is detected at one
side of impulse line.
See Note below this table.
It is applicable for DP Transmitter only.
OK: Blockage is not detected
BLOCKED: Blockage is detected at
Both sides of impulse line.
See Note below this table.
It is applicable for AP/GP Transmitter
only.
OK: Blockage is not detected
BLOCKED: Blockage is detected at
measurement side.
See Note below this table.
Displays the current status of PILD
algorithm i.e either Training mode or
Monitoring Mode.
See Note below this table
PILD factor for
blockage prediction
0.0 to 1.0
Displays the current PILD factor value.
See the Note below in table
Displays the training mode result.
NOTE: This diagnostics message or PILD sub menu will be visible only if PILD feature is supported
by the sensor and user enabled in the PILD option in the transmitter.