Page 40 ST 800 SmartLine Pressure Transmitters User’s Manual Revision 10
Note: Loop
must be
removed
from
Automatic
Control
This selection will calibrate the loop zero
output to 4.000 mA
Connect a current meter to the transmitter to
monitor the loop output.
When you press Enter, the transmitter will set
the loop output to 4 mA. When the prompt
“Enter reading” appears, enter the value
shown on the current meter (in milliamps) and
press Enter again. The transmitter will adjust
the DAC output to 4mA.
Press to enter
menu selection
Scroll to Trim Zero
or Trim Span
Press to initiate
and to select
number.
to enter and shift
to next digit
This selection will calibrate the loop span
output to 20.000 mA
Connect a current meter to the transmitter to
monitor the loop output.
When you press Enter, the transmitter will set
the loop output to 20 mA. When the prompt
“Enter reading” appears, enter the value
shown on the current meter (in milliamps) and
press Enter again. The transmitter will adjust
the DAC output to 20 mA.
This selection allows the loop to be returned
to its Normal mode (Automatic Control) after
performing the Trim operation.
Press to enter
menu selection
Scroll to Set DAC
Normal
Press to initiate
Note: Loop
must be
removed
from
Automatic
Control
This selection allows the user to force the
DAC output to any value between 3.8 and
20.8 mA.
Note: This selection will put the DAC into
Fixed Output Mode.
Press to enter
menu selection
Scroll to Set DAC
Output
Press to initiate
and to select
number.
to enter and shift
to next digit
This selection allows the loop to be returned
to its Normal mode (Automatic Control) after
performing the Set DAC Output operation
Press to enter
menu selection
Scroll to Set DAC
Normal
Press to initiate
Displays the calibration used by the
transmitter.
This selection
allows the user to
choose calibration
set from drop-down
menu,
Press to enter
menu selection
Press
and to select
calibration type.
to initiate
NOTES:
* "Cal Set B" item in menu is available only if sensor supports Dual calibration