Dehumidification configuration25
Dehumidification configuration
Table 9: Dehumidification configuration
Key
Options /
Range
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description
Cfg_Dehum_SpaceRHHighLimit0 to 10065 %RHBACnet
Numeric
Value
48Space Relative Humidity
(RH) High Limit setpoint.
Cfg_Dehum_MinOnTimeOpEnDisable (0)
Enable (1)
Disable
(0)
BACnet
Boolean
Value
12Minimum on Time Operation
Enable
Cfg_Dehum_MinOnTime240 to 1200
Secs
600 secBACnet
Numeric
Value
49Dehumidify Extended
Cooling Minimum on Time
Cfg_Dehum_MinOnDelay0 to 60
minutes
20
minutes
BACnet
Numeric
Value
98Dehumidification Minimum
ON time
Cfg_Dehum_StageReHeatOpEnDisable (0)
Enable (1)
Disable
(0)
BACnet
Boolean
Value
133Staged Reheat Operation