Control configuration31
Control configuration
Table 15: Control configuration
NameRange
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description
Cfg_Control_MainSensor1 = Local Temp/
Hum
2 = Remote
Temp/ Hum
3 = Multi Temp/
Hum
1 = Local
Temp/
Hum
BACnet
ENUM
Value
9Temperature/ Humidity
sensor selection.
Cfg_Control_PowerupDelay0-300 Sec10BACnet
Numeric
Value
14Initial delay to start control
after power cycle.
Cfg_Control_SmokeMode1 = No Override
2 = Shutdown
3 = Pressurize
4 = Depressurize
1 (No
Override)
BACnet
ENUM
Value
10When Smoke Monitor
state is on, the unit
operates as configured
through smoke mode