Recovery setpoint configuration35
Recovery setpoint configuration
Table 18: Recovery setpoint configuration
Key
Options /
Range
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description
Cfg_Recovery_MaxCoolRampRate
0 to 20
Δ°F/
hr
6 Δ°F/hr
BACnet
Numeric
Value
18Maximum Cooling
Setpoint Ramp
Cfg_Recovery_MinCoolRampRate
0 to 20
Δ°F/
hr
2 Δ°F/hr
BACnet
Numeric
Value
16Minimum Cooling
Setpoint Ramp
Cfg_Recovery_MaxCoolRampTemp-40 to 120
°F
70 °FBACnet
Numeric
Value
17Outdoor air
temperature at the
maximum cool setpoint
ramp.
Cfg_Recovery_MinCoolRampTemp-40 to 120
°F
90 °FBACnet
Numeric
Value
15Outdoor air
temperature at the
minimum cool setpoint
ramp.
Cfg_Recovery_MaxHeatRampRate
0 to 36
Δ°F/
hr
8 Δ°F/hr
BACnet
Numeric
Value
22Maximum Cooling
Setpoint Ramp
Cfg_Recovery_MinHeatRampRate
0 to 36
Δ°F/
hr
2 Δ°F/hr
BACnet
Numeric
Value
20Minimum Cooling
Setpoint Ramp
Cfg_Recovery_MaxHeatRampTemp-40 to 120
°F
60 °FBACnet
Numeric
Value
21Outdoor air
temperature at the
maximum heat setpoint
ramp.
Cfg_Recovery_MinHeatRampTemp-40 to 120
°F
0 °FBACnet
Numeric
Value
19Outdoor air
temperature at the
minimum heat setpoint
ramp.

Table of Contents

Other manuals for Honeywell TC500A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC500A and is the answer not in the manual?

Honeywell TC500A Specifications

General IconGeneral
BrandHoneywell
ModelTC500A
CategoryThermostat
LanguageEnglish

Related product manuals