32Multi-sensor configuration
Multi-sensor configuration
Table 16: Multi-sensor configuration
NameRange
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description
Cfg_ZoneMultiSens_C
ontrol
1 = Avg
2 = Min
3 = Max
4 = Smart
1BACnet
ENUM
Value
0Main control sensor configuration
Cfg_ZoneMultiSens_S
ens1_Wt
0 to 10
(0 = Disable)
10BACnet
Numeric
Value
33A weighted average allows individual
sensors to have more influence on the
average calculation. Sensor 1 is the local
on-board temperature sensor.
Cfg_ZoneMultiSens_S
ens2_Wt
0 to 10
(0 = Disable)
10BACnet
Numeric
Value
34A weighted average allows individual
sensors to have more influence on the
average calculation. Sensor 2 is the
remote TR40 Sylk temperature sensor
with Addr 2.
Cfg_ZoneMultiSens_S
ens3_Wt
0 to 10
(0 = Disable)
10BACnet
Numeric
35A weighted average allows individual
sensors to have more influence on the
Cfg_ZoneMultiSens_S
ens4_Wt
0 to 10
(0 = Disable)
1000%BACnet
Numeric
36A weighted average allows individual
sensors to have more influence on the
Cfg_ZoneMultiSens_S
ens5_Wt
0 to 10
(0 = Disable)
10BACnet
Numeric
37A weighted average allows individual
sensors to have more influence on the
Cfg_ZoneMultiHumSe
ns_Control
1 = Avg
2 = Min
3 = Max
4 = Smart
1BACnet
ENUM
Value
77Humidity sensor configuration
Cfg_ZoneMultiSens_H
umSens1_Wt
0 to 10
(0 = Disable)
10BACnet
Numeric
Value
181Weighted avg allows individual sensors to
have more influence on the avg
calculation. Sensor 1 is the on-board
Humidity sensor.
Zone humidity sensor weighting. 0 =
Sensor is disabled and not included in
average, min, and max calculations. 1 to
10 = Sensor is enabled. If sensor has a
valid reading, the sensor is included in
average, min, and max calculations.
W1 to w4 are weights of sensor1 to
sensor6 respectively.
H1 to H4 are humidity values of sensor1