58General network outputs
General network outputs
Table 29: General network outputs
NameRange
Default
Value
BACnet
Point Type
BACnet
Object
Instance
ID
Description
no_LocalOccSensState1=Occupied
2=Unoccupied
3=Unused
3=UnusedBACnet
ENUM Value
1Local Occupancy sensor
state
no_EffOccSensState1=Occupied
2=Unoccupied
3=Unused
3=UnusedBACnet
ENUM Value
2Effective Occupancy sensor
state
no_EffOccState1=Occupied
2=Unoccupied
3=Bypass
4=Standby
5=Null
5 = NullBACnet
ENUM Value
20Effective occupancy state.
no_ManualOverride1=Occupied
2=Unoccupied
3=Bypass
4=Standby
5=Null
5=NullBACnet
ENUM Value
4Manual Override
no_BypassState0=No Bypass
1=Bypass
No Bypass
(0)
BACnet
Boolean
Output
1Bypass State Output
no_BypassValue0-100NullBACnet
Numeric
Output
1Bypass Value output. 0=No
Bypass, 100=Bypass.
no_OccupancyState0=Unoccupied
1= Occupied
Unoccupie
d (0)
BACnet
Boolean
Output
3System is in occupied/
unoccupied state.
no_SmokeMode1=No Override
2=Shutdown
3=Pressurize
4=Depressuriz
e
1=No
Override
BACnet
ENUM Value
5Current smoke mode state.
no_SystemDisable0=Normal
1=Disable
Normal (0)BACnet
Boolean
Output
4System disable.
no_ServiceMd0=Disable
1=Enable
Disable (0)BACnet
Boolean
Output
5Service mode enable
no_EffDlcShift0-10 Deg FNullBACnet
Numeric
Output
2Effective Demand Limit Shift.
no_EffHeatSp40-120 Deg FNullBACnet
Numeric
Output
3Effective Heating Setpoint

Table of Contents

Other manuals for Honeywell TC500A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC500A and is the answer not in the manual?

Honeywell TC500A Specifications

General IconGeneral
BrandHoneywell
ModelTC500A
CategoryThermostat
LanguageEnglish

Related product manuals