42Alarm configuration
Alarm configuration
Table 23: Alarm configuration
Key
Options /
Range
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description
Cfg_Alarm_SupplyFan
AlarmConfig
Bits 0 False –
Don’t turn
off Heat/
Cool
Outputs
when alarm
is triggered
Bits 0 True –
Turn off
Heat/Cool
Outputs
when alarm
is triggered
Bits 0 =
True
BACnet
Numeric
Value
192The user shall decide whether to
enable or disable heating/ cooling
outputs when supply fan is in alarm
condition.
Cfg_Alarm_TempSens
AlarmConfig
Bits 0 False –
Don’t turn
off Heat/
Cool
Outputs
when alarm
is triggered
Bits 0 True –
Turn off
Heat/Cool
Outputs
when alarm
is triggered
Bits 0 =
True
BACnet
Numeric
Value
193The user shall decide whether to
enable or disable heating/ cooling
outputs when temperature sensor is
in alarm condition.