Sylk sensor configuration41
Sylk sensor configuration
Table 22: Sylk sensor configuration
Sylk
Address
NameRange
Default
Value
BACnet
Point
Type
BACnet
Object
Instanc
e ID
Description
2Cfg_Sylk_SylkBus2En1=Disable
2=TempOn
ly
3=Temp&H
um
4=Temp,
Hum &
CO2
Disable (1)BACnet
ENUM
Value
85Sylk Bus addr-2 device
enable/ disable
3Cfg_Sylk_SylkBus3En0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
147Sylk Bus addr-3 device
enable/ disable
4Cfg_Sylk_SylkBus4En0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
148Sylk Bus addr-4 device
enable/ disable
5Cfg_Sylk_SylkBus5En0=Disable
1=Enable
Disable (0)BACnet
Boolean
149Sylk Bus addr-5 device
enable/ disable
6Cfg_Sylk_SylkBus6En1=Disable
2=TempOn
Disable (1)BACnet
ENUM
86Sylk Bus addr-6 device
enable/ disable
8Cfg_Sylk_SylkBus8En0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
151Sylk Bus addr-8 device
enable/ disable
9Cfg_Sylk_SylkBus9En0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
152Sylk Bus addr-9 device
enable/ disable
10Cfg_Sylk_SylkBus10E
n
0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
153Sylk Bus addr-10 device
enable/ disable
11Cfg_Sylk_SylkBus11E
n
0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
154Sylk Bus addr-11 device
enable/ disable