52User non-configurable network inputs
User non-configurable network inputs
Table 26: User non-configurable network inputs
NameRange
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description
ni_NetSchCurrentState1=Occupied
2=Unoccupied
3=Bypass
4=Standby
5=No Override
5=No
Override
BACnet
ENUM
Value
1Current Schedule State from
Network.
ni_BypassState0=Disable
1=Enable
Disable (0)BACnet
Boolean
Value
1Net Bypass Input to enable
Bypass Timer
ni_BypassValue>=00BACnet
Numeric
Value
2Bypass Value to enable
Bypass Time
ni_DemandLimitContro
lEn
0=Normal
1=DLCEnable
Normal (0)BACnet
Boolean
Value
2Demand Limit Control (DLC)
input to limit the htg/ clg
demand.
ni_OccupancySensorSt
ate
1=Occupied
2=Unoccupied
3=Bypass
4=Standby
5=No Override
5=No
Override
BACnet
ENUM
Value
6Network Occupancy Sensor
State
ni_VOC_Level0-100 ppmNABACnet
Numeric
Value
90Network Input of Volatile
Organic Compound Level.
ni_OutsideTemp-40-150 Deg FNABACnet
Numeric
Value
89Network Outside Humidity
Value.
ni_OutsideHum0-100%RHNABACnet
Numeric
Value
194Network Outside
Temperature Value.
ni_ShutdownState0=Normal
1=Shutdown
Normal (0)BACnet
Boolean
Value
4System Shutdown input from
Network.
ni_SmokeMonitorstate0=Normal
1=Smoke
Normal (0)BACnet
Boolean
Value
5Smoke Detector Network
Input
ni_SpaceCO20-2000 PPMNABACnet
Numeric
Value
81Network Space CO2 Value.
ni_SpaceRH0-100%RHNABACnet
Numeric
Value
80Network Space RH Value.
ni_SpaceTemp-40-200 Deg FNABACnet
Numeric
Value
104Network Space Temperature
Value.