66BACnet object used for alarm
AlarmPriority_AirFlwFaultBACnet
Boolean
Output
710 = Nml
1= Med
Priority
Air Flow Status Physical Input Alarm
Priority
Alarm_UI_ShutdownBACnet
Boolean
Input
6Actual Alarm
point is
AlarmPriority
_ShutdownFa
ult
Shutdown Physical Input
Alarm_UI_ShutdownBACnet
Boolean
Input
6Actual Alarm
point is
AlarmPriority
_ShutdownFa
ult
Shutdown Physical Input
AlarmPriority_ShutdownFaultBACnet
Boolean
Output
720 = Nml
1= Med
Priority
Shutdown Physical Input Alarm Priority
Alarm_UI_CO2LvlBACnet
Numeric
Input
7Actual Alarm
point is
AlarmPriority
_CO2LvlAlar
m_Fault
CO2 Level Physical Input
AlarmPriority_CO2LvlAlarm_Faul
t
BACnet
ENUM
Value
121 = Nml
2 = Med
Priority (Out
of Range)
3 = High
Priority
(Sensor
Failure)
CO2 Level Physical Input Alarm Priority
Alarm_UI_WtrFlwStsBACnet
Boolean
Input
7Actual Alarm
point is
AlarmPriority
_WtrFlwFault
Water Flow Status Physical Input
AlarmPriority_WtrFlwFaultBACnet
Boolean
Output
730 = Nml
1= Med
Priority
Water Flow Status Physical Input Alarm
Priority
Alarm_UI_CompDASensBACnet
Numeric
Input
14Actual Alarm
point is
AlarmPriority
_DATempAlar
m_Fault
Comp Discharge Air Temperature Physical
Input
Table 30: BACnet object used for alarm (Continued)
Key
BACnet
Point
Type
BACnet
Object
Instance
ID
PriorityDescription