Situational BACnet guidelines for TC500A71
PICS statementReference input and output
is claimed in the PIC
statement, but the
corresponding objects is not
there in thermostat
NANA
Output Object Read /
Write
Priority array values are not
synchronized with actual for
AO, MSO, & BO in Niagara
NANA
Output Object Read /
Write
Set operation on AO, BO &
MSO is writing values to the
priority-16 instead of
relinquish default
NANA
Output Object Read /
Write
If user configure binary
input or output in UIO
terminal and the
corresponding values has to
be refereed in analog input
or output object instead of
binary input or output in
Niagara
NANA
FIRMWAREThermostat firmware &
application download does
not support by Niagara
(start restore and end
restore service is missing)
NA3rd party tool like
YABE can be used for
firmware download
Table 31: BACnet guidelines for TC500A (Continued)
FeatureLimitation / BehaviorDescriptionWorkaround