44
VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
PROMPT EXPLANATION
010 ACCESS POINT
(00-15) 01
If response type 27, or 29 was selected, this prompt will be displayed.
Enter the access point to be controlled by the input type (00-15 for type 27; 01-15 for type 29).
NOTE: If you are using the VistaKey module, the access point must match the address that was set in
the module.
Press [∗] to continue.
010 ENTRY OR EXIT
0
If response type 27, or 29 was selected, this prompt will be displayed.
Enter whether the access point is an entry or exit point.
0 = entry; 1 = exit
Press [∗] to continue.
010 Partition
1
Enter the partition number (1–8) you are assigning this zone to (2∗00 must be enabled if using
multiple partitions).
Press [∗] to continue.
010 REPORT CODE
1st 03 2nd 12 3C
Enter the report code.
The report code consists of 2 hexadecimal digits, each consists of 2 numerical digits. For example, for
a report code of "3C," enter 03 for "3" and 12 for "C."
(Refer to the System Communication section in the Installation and Setup Guide for more information
about report codes and reporting formats.)
Press [∗] to continue.
010 INPUT TYPE
RF Xmitter 3
Input types 4 & 5 are
valid for certain 5800
Series transmitters only.
If using input type 02
with a door/window type
transmitter, only loop 1
may be used.
If you selected response
type 29 the input type
MUST be 00.
Enter the input device type as follows:
00 = Not Used 07 = DIP switch-type polling loop device
08 = Right loop of DIP switch type device
02 = RF motion (RM type) 09 = Keypad input (code + #73)
03 = Supervised RF transmitter (RF type) 10 = Not Used
04 = Unsupervised RF transmitter (UR type) 11 = VistaKey Door Status Monitor (DM)
05 = RF button-type transmitter (BR type) 12 = VistaKey Request to Exit (RE)
06 = Serial number polling loop device (SL type)
13 = VistaKey General Purpose (GP)
NOTE: Input types 11 (DM), 12 (RE), and 13 (GP) should only be used with VistaKey modules.
Press [∗] to continue.
010 SMART CONTACT
1 = YES 0 = NO 0
If input type 3 or 6 was selected, this prompt will be displayed.
Enter 1 = For devices that monitor maintenance signals (ex. 5193SD, 5193SDT) or can be used to
limit fault signals in the disarmed state (ex. IS2500SN).
Enter 0 = Disabled
NOTES:
• The Smart Contact option must ONLY be selected for devices that support the feature, otherwise
unpredictable results may occur.
• If using the new 5193SD/SDT V-Plex smoke detectors, the "Smart" option must be selected in
zone programming. If not, unpredictable results may occur if the smoke goes into a High Sens or
Low Sens condition.
010 ANTI MASK
1 = YES 0 = NO 0
If zone type is 04 (interior) or 10 (interior with delay) and input type 06 (serial poll) is selected, this
prompt displays.
If enabled the device, such as a DT7500SN, supporting the Anti-Mask processing reacts if someone
covers, paints, or otherwise blocks the lens of the PIR from seeing it’s field of view.
The control processes this message as a special “anti-mask” trouble, including rapid trouble beeping.
The control displays MASKED with the zone number on the keypad, and a trouble on the zone is sent
to the central station, if programmed. This feature is enabled by a dip switch on the DT7500SN,
otherwise refer to the installation instructions of the device.