Installing the HP UPS Power Protection Agent  36 
The installer launches a separate configuration program. 
 
The script displays: Please enter a server to allow connections from. 
2.  Enter the IP address of the management module or the path to the serial device. This configuration 
ensures that only that particular management module executes commands and operating system 
shutdowns on the computer running the agent. 
The script displays: Please enter a second server to allow connections from. 
3.  Enter the IP address of a second management module or the path to the second serial device for 
redundant communication. 
 
 
IMPORTANT: If you are configuring redundant management modules, do not enter an 
asterisk to allow any server to connect to the management module. 
 
If you do not want to configure a second connection, enter None. 
 
Installing the agent using the silent installation method 
Silent installation is typically used by system administrators who have many installations that are 
configured identically and require minimal user interaction. During a silent installation you will: 
•  Install an agent through the assisted installation method that is appropriate for the operating system. 
•  Configure the agent exactly as the final replicated systems should be configured. 
 
 
NOTE: You must configure the IP address of the management module. Create a 
DevManRA.ini file for each site. This points each agent to the correct management module 
and is the more secure option. 
 
•  Use the DevManRA.ini file that is generated in the directory of the application as a template in the 
agent silent install process.