Troubleshooting  94 
Event notifications are not being sent 
Action:  While email and SNMP trap notifications must be set up on their respective screens, notifications 
must also be enabled per event on the Event Notifications screen ("Event Notifications menu" on page 
67). 
 
FTP error messages appear when connecting 
through Linux 
Symptom: When connecting to FTP through Linux, error messages about bad commands appear. 
Action: The user can log in although the error messages appear. 
 
Flash update fails over a serial connection 
Action: Disable any serial port being configured during the flash update, such as iLO, or use an FTP 
connection. 
 
HP SIM lists a discovered UPS as Unmanaged in the 
System Type column 
Action:  
1.  Delete the discovered UPS from HP SIM. 
2.  Using the management module web interface, add the HP SIM server as a Manager on the SNMP 
Managers tab (on page 65). 
3.  Rediscover the UPS in HP SIM. 
 
HPFlash does not install image.bin on a Pentium III 
Symptom: The image.bin file is not installed on a Pentium III during a serial upgrade. 
Possible Cause: The minimum hardware requirement for HPFlash is Pentium 4. 
Action: Be sure that the hardware meets the minimum HPFlash requirements. 
 
Initiate Battery Test Command Has Been Sent 
message not displayed 
Action: View the results of the battery test on the Application Log screen ("Application Log menu" on page 
58).