4.3.2.2 Connecting Cabinet Input Power Cables
Context
The power distribution subrack position in the cable connection
gure is for
reference only. The actual position may vary.
Procedure
Step 1 (Optional) Connect input power cables to the PDU.
1. (Optional) Remove the transparent protective panel at the rear of the PDU.
2. Connect input power cables to the PDU.
Figure 4-57 Connecting input power cables to the PDU
----End
4.3.2.3 Connecting rPDU Power Cables
Context
The rPDU complying with China standards or IEC can be congured based on site
requirements.
If the rPDU is not
congured with industrial connectors, connect the rPDU cables.
Procedure
Step 1 Connect cabinet rPDU cables.
1. Connect the rPDU enclosure ground cable.
2. Remove the front panel from the rPDU.
3. Connect one end of the reserved rPDU power cable to the rPDU terminal
block, and the other end to the power distribution subrack.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 4 Installation Guide
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 94

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 Smart and is the answer not in the manual?

Huawei FusionModule500 Smart Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500 Smart
CategoryStorage
LanguageEnglish

Related product manuals