6.1.2 Quarterly Maintenance
Table 6-2 Quarterly preventive maintenance table
Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
Power supply and
distribution
system
Operating status
of the surge
protection module
Check the surge
protection
module indicator
and MCB status.
The surge
protection
module
indicator is
steady green.
The MCB is
switched on.
If the surge
protection
module
indicator is
red, replace
the surge
protection
module.
If the MCB is
o, switch it
on.
UPS Operating
environment
- Ambient
temperature:
0°C to 40°C
Humidity:
0%–95% RH
(non-
condensing)
If the
temperature
or humidity
is abnormal,
check the
smart
cooling
product
status.
If the input
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
LCD - According to the
status icons on
the LCD, all units
are operating
properly. No
fault or alarm
information is
found in the
active and
historical alarm
records.
If an alarm is
present, rectify
the fault by
checking the
device status
and parameters.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 6 O&M
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 154

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 Smart and is the answer not in the manual?

Huawei FusionModule500 Smart Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500 Smart
CategoryStorage
LanguageEnglish

Related product manuals