Figure 5-10 Removing the fastener
If the door still cannot be opened or closed properly, check the following items:
● Whether cables are connected correctly
● Whether the DIP switch setting is correct
----End
5.3.9 Conguring Event Notication
You can set alarm notication by email or SMS as required. Information about a
maximum of 20 users who will receive alarm
notication can be displayed.
Prerequisites
To implement alarm notication by SMS, the following conditions must be met:
● The ECC800-Pro is congured with a 4G module and supports standard SIM
card access.
● The ECC800-Pro is connected to a network with an email server through a
WAN port. Both the Internet and local area network (LAN) are supported.
To use the WeChat notication function, connect the ECC800-Pro to the EDCM system. For
details, see the user guide of the EDCM system.
Procedure
Step 1 Choose System Settings > Event Notication.
Step 2 Set related outbox parameters.
1. Set related parameters in the Outbox Settings area on the Mailbox Settings
page. If the address type of the outbox is Domain name, choose System
Settings > System Parameters, and set related parameters in the DNS
Server Address area on the Monitor IP page.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 5 Power-On Commissioning
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 127