Item Specications
Humidity precision ±5% RH (25°C, 20%–80% RH)
Operating temperature –20°C to +70°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +70°C
Output RS485
3.4.3.2.3 Smoke Detector
A smoke detector detects smoke around cabinets.
Figure 3-15 Smoke detector
Table 3-28 Smoke detector technical specications
Item
Specications
Operating voltage 9–27 V
Alarm current < 20 mA
Indication Monitoring: The red indicator blinks
once every 3 to 8 seconds.
Alarm reporting: The red indicator is
steady on.
Operating temperature –10°C to +55°C
Ambient humidity ≤ 95% RH
Dimensions (H x W x D) 31 mm x 75 mm x 51 mm (with the
base)
Weight 50 g
3.4.3.3 Cabinet Electronic Clasp Lock
The cabinet electronic clasp lock is used to manage access control. It can be
automatically unlocked, or manually locked and unlocked.