Check Item Specications Check Result
Equipment room
height
≥ 2.6 m □ Passed □ Failed
Equipment room
area
≥ 10.15 m
2
□ Passed □ Failed
Equipment room
maintenance
clearance
At least 1200 mm, 1000 mm,
and 1000 mm maintenance
clearance should be reserved
from the front door, rear, and
side of the cabinet, respectively.
At least 100 mm clearance
should be reserved from the
wall.
□ Passed □ Failed
Power system 208–240 V 1Ph 50 Hz/60 Hz □ Passed □ Failed
Water port Condensate drain outlet: Drains
condensate water from the
smart cooling product.
□ Passed □ Failed
Figure 4-1 Space requirements
NO TE
If any of the requirements is not met, contact Huawei technical support.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 4 Installation Guide
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 57