Procedure
Step 1 Shut down the air conditioner over the EMS.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a. Choose Home.
b. Tap the cabinet that houses the air conditioner in the micro-module view.
c. Tap the air conditioner to be set in the cabinet layout diagram.
d. Choose Real-time Data > OFF.
Method 2: Log in to the ECC800 WebUI as admin. Choose Monitoring > Air
Conditioner > NetCol5000-A0104 > Controls > Ctrl Info, set On/off status on
EMS > Off, and then click Submit.
0104 in NetCol5000-A0104 is variable and subject to changes with the air conditioner connection
sequence. The displayed value prevails.
Step 2 Disconnect the power supplies from the air conditioner control unit and the outdoor unit after
the air conditioner shuts down over the EMS.
Step 3 Open the top cover, front panel, and left front panel using a screwdriver, as shown in Figure
5-40.
Figure 5-40 Removing a panel
Step 4 Cut the cable ties on the fan cable using diagonal pliers and take out the outdoor fan cable
from the electric control box.

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals