Category Specications
Altitude ● Operating altitude ≤ 3050 m (10006.44 ft)
If the server complies with ASHRAE Class A2, the
maximum operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.25 ft) in
altitude above 900 m (2952.76 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
● Titanium PSUs are required for the altitude higher
than 3050 m (10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
Particle contaminant ● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the
equipment room be monitored by a professional agency.
3.3 Physical Specications
Table 3-3 Physical specications
Category
Description
Dimensions (H x W x
D)
40.5 mm x 177.9 mm x 545.5 mm (1.59 in. x 7.00 in. x
17.89 in.)
Weight in full
conguration
● Net weight: 4.2 kg (9.26 lb)
● Packing material weight: 2.73 kg (6.02 lb)
Power consumption The power consumption parameters vary with
hardware congurations (including the congurations
complying with EU ErP). Use the Computing Product
Power Calculator to obtain specic information.
FusionServer Pro XH321 V5 Server Node
Maintenance and Service Guide 3 Product Specications
Issue 17 (2021-03-09) Copyright © Huawei Technologies Co., Ltd. 28