6 Checking Before Power-On
Item No. Check Item Acceptance Criteria
Gene
ral
inspe
ction
1 Equipment appearance ● The equipment is intact and free from
rust or paint ake-o. If paint akes o,
repaint the equipment.
● The labels on the equipment are clear.
Damaged labels must be replaced.
2 Cable appearance ● Cable sheathings are properly wrapped
and not damaged.
● Cable hoses are intact.
3 Cable connections ● Cables are connected in the designed
positions.
● Terminals are prepared as required and
securely connected.
● Labels on both ends of each cable are
clear and
specic, and attached in the
same direction.
4 Cable layout ● Electrical and ELV cables are routed
separately.
● Cables are neat and tidy.
● Cable tie joints are evenly cut without
burrs.
● Cables are placed properly and reserve
some slack at bending points to avoid
stress.
● Cables are routed neatly without twists
or crossovers in the cabinet.
5 Switch ● The DC LV Panel switch is set to OFF.
● The battery rack switch is set to OFF.
LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual 6 Checking Before Power-On
Issue 02 (2021-11-15) Copyright © Huawei Technologies Co., Ltd. 104