4.2.4 Grounding the ESS
Prerequisites
CA UTION
The grounding should comply with the local electrical safety regulations.
Do not connect devices such as fuses and switches to ground cables.
Connect ground cables to the ground points of the ESS enclosure or the main
ground bar of the control unit cabin based on site requirements.
The ESS is installed.
The grounding requirements are clear.
Context
The ESS can be grounded using ground lugs or ground cables. The requirements
are as follows:
Ground lug: Use ground lugs made of hot-dip zinc-coated
at steel with a
cross-sectional area of 40 mm x 4 mm, and the concrete platforms must be
300 mm above the ground.
Ground cable
Table 4-3 Ground cable description
No.
Cable Type Cross-
Sectional
Area
Outer
Diameter
Source
1 Ground
cable
Single-
core
outdoor
copper
cable and
M12
OT/DT
terminals
16–240
mm
2
10–32 mm Prepared
by the
customer
The specications of the ground cable are subject to this table or calculated
according to IEC 60364-5-54.
Connect ground cables
Method 1Connect ground cables to the ground points of the ESS enclosure
Step 1 Connect ground cables to the ground points of the ESS using M12x30 stainless
steel bolt assemblies. The ground cables can be routed through plastic-coated
metal hoses based on site requirements.
LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual 4 Installation
Issue 02 (2021-11-15) Copyright © Huawei Technologies Co., Ltd. 78