3 Site Requirements
3.1 Site Selection Requirements
The ESS applies to outdoor scenarios. The site selection requirements are as
follows:
● Transportation to the site is convenient and the site
re protection facilities
are reliable.
● The site area must meet the requirement and there is space for capacity
expansion.
● The ground should be solid without spongy or soft soil, and should not be
prone to water accumulation or subsidence.
● The site is in a well-ventilated place.
● The site is in a stable area far away from high-levels of noise and
electromagnetic interference.
● The site is not above any underground facilities.
● The site is far away from dust, oil, smoke, harmful gases, and corrosive,
ammable, or explosive objects.
● The site is at least 500 m away from any airports, landlls, and water areas.
● The site is an open area and at least 10 m away from any obstacles in all
directions.
● The site is at least 50 m away from residential areas.
● The site should not be located in a low-lying land. The horizontal level of the
site should be above the highest water level of that area.
3.2 Space Requirements
Clearance must be reserved for installation and O&M, as required in the following:
● Reserve at least 3 m and 2 m clearances on the long and short sides of the
ESS respectively.
LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual 3 Site Requirements
Issue 02 (2021-11-15) Copyright © Huawei Technologies Co., Ltd. 65