2.8.4.4 Fire Control Panel
Figure 2-39 Appearance of the re control panel
Table 2-32 Technical specications of the re control panel
Technical Specications Fire Control Panel
Model K11031M2
Dimensions (H x W x D) 385 mm x 310 mm x 90 mm
Operating voltage ● 230 V+10%/-15% AC
● Two 12 V 7Ah sealed lead acid in series
Power AC Input ≤ 100 W
Capacity ● No. of detection circuits: 3
● No. of detector per zone: ≤ 32
Detector loop
requirements
● Wire system of the detector loop: two-wire
system
● Length of the detector loop: ≤ 1000 m
Enclosure material 1.2 mm mild sheet steel
Operating temperature -5°C (±3°C) to +55°C (±2°C)
Humidity ≤ 95% RH (non-condensing)
IP rating IP30