8 SmartLogger Web-based Deployment
Prerequisites
1. All devices onsite have been commissioned.
2. The system is powered on and alarms are cleared.
3. The commissioning equipment is available onsite.
4. Before the deployment, wait until the air conditioner adjusts the temperature
inside the cabinet and the temperature of batteries to the
specied
temperature range (5°C to 45°C).
8.1 Preparations and WebUI Login
Prerequisites
● The operating system of Windows 7 or later is supported.
● Browser: Chrome 52, Firefox 58, or Internet Explorer 9, or a later version is
recommended.
Procedure
Step 1 Connect the network cable between the network port of the PC and the WAN or
LAN port of the SmartLogger.
Step 2 Set the IP address for the PC on the same network segment as the SmartLogger IP
address.
Connected
Port
Item SmartLogger
Default Value
Example PC
Setting
LAN port IP address 192.168.8.10 192.168.8.11
Subnet mask 255.255.255.0 255.255.255.0
Default gateway 192.168.8.1 192.168.8.1
WAN port IP address 192.168.0.10 192.168.0.11
Subnet mask 255.255.255.0 255.255.255.0