10 Alarm Reference
Alarm severities are dened as follows:
● Major: The equipment is faulty. As a result, the output power decreases or the
grid-tied power generation is stopped.
● Minor: Some components are faulty without aecting the grid-tied power
generation.
● Warning: The equipment works properly. The output power decreases or some
authorization functions fail due to external factors.
Table 10-1 CMU common alarms and troubleshooting measures
Alar
m ID
Alarm
Name
Severit
y
Possible Causes Troubleshooting Suggestions
3800 Water
alarm
Major Cause ID=1
Water leaked into battery
compartment.
1. Check whether water leaks into the
container.
2. Check whether water leaks into the
battery compartment.
Cause ID=2
Water leaked into power
distribution compartment.
1. Check whether water leaks into the
container.
2. Check whether water leaks into the
power distribution compartment.
3801 Door
Status
Alarm
Warnin
g
Cause ID=1- 6
Battery compartment
doors 1-6 are open.
Cause ID=7
Power distribution
compartment door is
open.
-
3802 Fire
Alarm
Major Cause ID=1
Smoke or overheating
detected in battery
compartment.
Check whether smoke or re occurs in
the battery compartment of the
container. If yes, press the emergency
re protection start button. If not,
reset the system.
LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual 10 Alarm Reference
Issue 02 (2021-11-15) Copyright © Huawei Technologies Co., Ltd. 134