Alar
m ID
Alarm
Name
Severit
y
Possible Causes Troubleshooting Suggestions
3817 Air
Condition
er
Condense
r
Temperat
ure
Sensor
Fault
Minor
3818 Air
Condition
er
Ambient
Temperat
ure
Sensor
Fault
Minor
3819 Air
Condition
er
Evaporat
or Frozen
Minor Cause ID=1-13
1. The air intake or
exhaust is blocked.
2. The indoor fan is
faulty.
3. The cooling system
cannot be shut down
in a timely manner.
4. The evaporator
temperature sensor is
faulty.
1. Check that the air intake vent and
air exhaust vent of the equipment
room are not blocked.
2. Check whether the indoor fan
works properly.
3. Check the main control board of
the cooling system and related
electrical control.
4. Replace the temperature sensor.
5. If the fault persists, contact your
dealer or Huawei technical support.
3820 Frequent
Air
Condition
er System
High
Pressure
Alarm
Major Cause ID=1-13
1. The condenser is
blocked or has scale.
2. The condenser fan is
faulty.
3. The external air
ow
experiences a shortcut
or is blocked.
1. Clean the outdoor heat exchanger.
2. Repair or replace the outdoor fan.
3. Check whether there are obstacles
in front of the air or exhaust vent of
the outdoor fan.
4. If the fault persists, contact your
dealer or Huawei technical support.
LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual 10 Alarm Reference
Issue 02 (2021-11-15) Copyright © Huawei Technologies Co., Ltd. 138